Specifications include, but are not limited to: A. DAY TANK INSPECTION Check all day tanks and pumps for proper fluid flow. Make any adjustments that are required. B. ANNUAL FUEL SYSTEM ANALYSIS 1) A sample of the diesel supply fuel in each one of Orange County Convention Center’s diesel tanks (100 gallons and above) shall be taken and submitted to a laboratory for analysis annually. If the diesel supply fuel in any one of the tanks receives a negative analysis, that tank’s fuel shall be polished through a polishing process that removes at least 99% of all water and solids greater than five (5) Microns. After fuel polishing, a fuel treatment/stabilizer shall be added to each fuel tank. This treatment shall prevent algae growth, be a moisture inhibitor and provide fuel stabilization. The amount of treatment/stabilizer shall be proportional with the fuel level in the tank. The cost of the fuel analysis shall be billed against line Fuel Recycling (Polishing) Cost per Gallon to Recycle, Additional Services Table. The cost of the polishing and fuel treatment shall be billed per line item Additional Fuel Analysis (Independent Laboratory), Additional Services Table. Labor charges shall not apply. 2) If the Annual Fuel Analysis showed that fuel polishing needed to be performed, the tank or tanks that were polished will be subject to random sampling to confirm the fuel quality. The Facility Operations Manager or designee shall choose at most, two (2) tanks from those that have been polished that will have fuel samples drawn and another analysis done to determine the quality and effectiveness of the fuel polishing and treatment.