The District of Columbia Office of Contracting and Procurement, on behalf of The District of Columbia’s Department of Corrections (DOC) (the “District”) is seeking the replacement of two (2) uninterrupted power supply (UPS) units for the Central Detention Facility (CDF) and Central Treatment Facility (CTF). The contractor shall replace the existing 40kVA GE UPS in Electrical Grade Room G124 with: a. Eaton 93PM 40kW UPS; 1 Output Rating (kW): 40kW; 2 Qty of 20kW Power Modules: 3 2 UPS Frame Capacity: 4 60 kW Input Voltage: 5 208V Single Feed Input to the UPS: 6 Hardwired Output from the UPS: 7 Hardwired Double Conversion Topology 3-Breaker Sidecar Maintenance Bypass Multilanguage Display UPS Dimensions: 8 Dimensions: 34.5” W x 42” D x 74” H UPS Weight:639 Pounds; 9 Network Card: Eaton Industrial Gateway Communications Card; b. The equipment shall include startup: 7X24 Monday thru Sunday; c. The equipment shall include a warranty: 12 Months from date of startup or 18 months from date of shipment. d. The contractor shall provide an Eaton UPS Battery Cabinet (Qty. 1): 1 DC Voltage: 480VDC; 2 Battery Runtime:20 Minutes at 40kW; 3 Weight: 2195 Pounds; 4 Dimensions: 16.7” W x 42” D x 74” H; The contractor shall replace the existing 5.3kVA Eaton FerrUPS units in the IT closet near Security, with: a. Eaton 9PXM 8kVA UPS (Qty. 1): 1 Output Rating (kVA): 8kVA; 2 Qty of 4kVA Power Modules: 2 Battery; 3 Module Quantity: 8; 4 Voltage:110V/120V, 120/208V, 120/240V, 127/200V Single Feed Input to the UPS: 5 Hardwired Output from the UPS: 6 Hardwired 17 Minute Battery Runtime Wall-Mounted Maintenance Bypass Panel; 7 Modular Design – Expandable Runtime Rack/Tower Convertible; 8 UPS Dimensions:17.5” W x 34.5” D x 25” H UPS Weight: 185 Pounds; 9 Network card; b. The equipment shall include startup: 7X24 Monday thru Sunday; c. The equipment shall include a warranty: 12 Months from date of startup or 18 months from date of shipment.