Specifications include, but are not limited to: 1.0 POWER GENERATION SYSTEM A. Requirements: 1. Kohler Generator Set, sized as required, or approved Equal. 2. Power Factor: 0.8 4. Hertz: 60 at 1800 revolutions per minute. 5. Temperature Rise: 130 degrees C (standby) 6. Deliver full load amps with up to 5% total harmonic distortion. 7. Generator Output Voltage 120/208V, 3-Phase, 9. Shall comply with NEMA MG1, applicable IEEE and ANSI standards for temperature rise and motor starting. 1.1 ENGINE A. General Requirements: 1.Fuel: Diesel. 2. Cooling: Liquid Cooled. 3. Engine Speed: 1800 revolutions per minute. 4. Governor: Electronic. 5. Emissions: Unit shall be manufacturer certified as compliant with Delaware Code, Title 7, Regulation 1144 – Control of Stationary Generator Emissions. Vendor shall include documentation of such certification in bid package. B. Provide the following accessories: 1. Fuel filter. 2. Sound Enclosure 3. Weather Enclosure 4. Battery charger with alarms 5. Line circuit breaker (NEMA1 enclosure) 6. Gages: a. Fuel pressure b. Water temperature c. Lube oil pressure C. Starting: 1. Quantity and voltage of starter motors in accordance with manufacturer’s instructions. 2. Selector switch with start button on control panel. 3. Cranking motor: a. Heavy duty that automatically engages and releases from flywheel without binding. D. Safety Devices: 1. Engine shutdown on the following (limits selected by manufacturer): a. High Coolant temp b. Low oil pressure c. Over-speed d. Engine over-crank