Specifications include, but are not limited to: 1. Founders Bridge Adrien’s Landing Pump Station Contractor shall Perform the following: Inspect, test run and provide preventative maintenance to the generator in accordance with the Annual Generator Maintenance Required Work and Inspection Checklist attached as Schedule 1 to this Exhibit A. Pull each pump and inspect for internal and external problems. Remove volute from pump, inspect impeller and wear ring to manufacturer’s specifications. Inspect condition of oil in each pump and flush valve. Reassemble and reinstall pump and check amperage and ohms. Remove any floating debris from third level of pump station. Check operation and condition of floats and level sensors. Check and calibrate gas detection sensors and test. Test and verify alarm conditions. Check and test electrical breaker systems. Clean and test dehumidifier. Clean and test heating system. Check operation of equipment including hoist systems and their motors. Prepare detailed report of findings and repairs. Repairs required on any of the pump station equipment must be Performed with prior Client Agency approval. 2. Rte. 372, Berlin Pump Station: Contractor shall Perform the following: Inspect, test run and provide preventative maintenance to the generator. Pull each pump and inspect for internal and external problems. Remove volute from pump, inspect impeller and wear ring to manufacturer’s specifications. Inspect condition of oil in each pump and flush valve. Reassemble and reinstall pump and check amperage and ohms.