A. Test, adjust, and balance the following: 1. Heating Coils. 2. Fans. 3. Air Filters. 4. Air Terminal Units. 5. Air Inlets and Outlets. 3.09 MINIMUM DATA TO BE REPORTED A. Heating Coils: 1. Identification/number. 2. Location. 3. Service. 4. Manufacturer. 5. Air flow, design and actual. 6. Water flow, design and actual. 7. Water pressure drop, design and actual. 8. Entering water temperature, design and actual. 9. Leaving water temperature, design and actual. 10. Entering air temperature, design and actual. 11. Leaving air temperature, design and actual. 12. Air pressure drop, design and actual. B. Return Air/Outside Air: 1. Identification/location. 2. Design air flow. 3. Actual air flow. 4. Design return air flow. 5. Actual return air flow. 6. Design outside air flow. 7. Actual outside air flow. 8. Return air temperature. 9. Outside air temperature. 10. Required mixed air temperature. 11. Actual mixed air temperature. 12. Design outside/return air ratio. 13. Actual outside/return air ratio. 14. C. Duct Traverses: 1. System zone/branch. 2. Duct size. 3. Area. 4. Design velocity. 5. Design air flow. 6. Test velocity. 7. Test air flow. 8. Duct static pressure...