AHEC intends to purchase pumps to replace existing storm and sewer ejector pumps for the following locations on campus:
Library South Vertical Sewage Pumps (2);
Requirements: Cover-mounted vertical sewage pump, graphite bearings, Level transducer, Failsafe float switches (20 FT mercury); Weil Model W-2108 (or approved equal providing submittal that meets the requirements stated in this description).
Library North Vertical Sewage Pumps (2),
Requirements: Cover-mounted vertical sewage pump, graphite bearings, Level transducer, Failsafe float switches (20 FT mercury). Weil Model W-2108 (or approved equal providing submittal that meets the requirements stated in this description).
Media Center Vertical Sump Pumps (2);
Requirements: Cover-mounted vertical sewage pump, graphite bearings; Weil Model W-1200 (or approved equal providing submittal that meets the requirements stated in this description).
King Center Foundation Vertical Sump Pumps (2);
Requirements: Cover-mounted vertical sewage pump, graphite bearings, Level transducer, Failsafe float switches (20 FT mercury); Weil Model W-2108 (or approved equal providing submittal that meets the requirements stated in this description).
King Center Sewage Pumps (2);
Requirements: Cover-mounted vertical sewage pump, graphite bearings, Level transducer, Failsafe float switches (20 FT mercury); Weil Model W-1226 (or approved equal providing submittal that meets the requirements stated in this description).
Domestic Water Booster Pumps in Science (3)
Requirements: variable control 10 HP pumps, NEMA 4 rated, with one (1) control panel with 2 isolation valves, 1 check valve, 1 thermal purge valve and spool pieces; VC Model 3VC-PMC-V-10-630-460 (or approved equal providing submittal that meets the requirements stated in this description).
Tivoli Vertical Sewer Pump (1)
Requirements: Cover-mounted vertical sewage pump, graphite bearings, Weil Model W-2108S (or approved equal providing submittal that meets the requirements stated in this description).