Specifications include, but are not limited to: As needed Waste Water Pump Equipment Repair services as specified herein for the California Department of Corrections and Rehabilitation located at the California State Prison - Corcoran, 4001 King Avenue, Corcoran, CA 93212. Services to be performed by the Contractor shall include the following: A. Pump and motor alignment to be within .005” B. Replace worn wear rings if clearance is excessive or a drop in efficiency has occurred C. Each repair will include, but is not limited to, the following Check wear ring clearances and repair as needed Check bearing fits and repair as needed to manufacturer’s specifications. Install new bearings Water test pumps to no less than 50 psi Check shafts for straightness and straighten if shaft exceeds factory specification or industry standards Ensure all tolerances are returned/set to Operations Equipment Manual (OEM) specifications. Ensure compression meets OEM specifications. Check all electrical wire connections for loose connections and or corrosion buildup on terminals and repair as needed. Any parts requiring replacement will be replaced in accordance with the Parts Replacement Section specified herein.