Specifications include, but are not limited to: Filter fuel in tank using 5-micron or smaller filter element by removing all foreign particles and microbial organisms. AST cleaning & water removal using fuel/water separator. Tank removal layers of sedimentation by aggressively agitating the tank using powerful pump system. Removal and disposal of hazardous waste and waste fuel (waste should be disposed and transported out of Catalina Island) Before and after tank bottom fuel samples Vendor to provide labor, tools, disposal containers and transport to the site. Manifesting and Profiling of Waste (if any) All areas accessed or disturbed during the process will be cleaned, secured and/or returned to their original condition. The compliance review will include but is not limited to the following scope of work. • Photo document all tanks, equipment, pumps and day tanks. • Record all equipment manufacturer names, model numbers and serial numbers. • Inspect each system for the following: • All emergency and normal venting in place