Specifications include, but are not limited to: D. Field Data Collection equipment shall include: i. Field Transformers, Switches, and ATS’s (125) ii. Main Switchgear Board iii. Metering Section iv. Switches at Main switch switchgear v. Feeder switches in Main Electrical Room (8) E. Information needed for the Field Data Collection, at each site shall include the following: i. Conductors: Type, size, length, insulation type, conduit size and conductors per phase. ii. Circuit Breakers: Manufacturer, model, frame amp and voltage rating, interrupting capability, and adjustable trip settings (if applicable). iii. Relays (50/51): Manufacturer, model, Current Transformer ratio and Tap settings, settings. iv. Fuses: manufacture, type, continuous ampere rating, short circuit interrupting rating, and voltage rating. v. Transformers: Nameplate rating, primary-secondary winding configuration and voltages, neutral grounding resistor rating (if used), X/R ratio, and percent impedances (%Z). vi. Alternating Current induction motors: Horsepower, voltage, Full Load Amps, power factor, efficiency, number of poles and rated synchronous speed. vii. Switchgear, Motor Control Centers, Panel Boards: Manufacturer, model, voltage rating, continuous ampere rating, number of phases, number of wires, and bus brace rating. viii. Utility data including: source impedance, available fault current, and upstream protective device settings.