• Category 6A UTP 4 Pair: o Shall be Category 6A Plenum rated cabling (General Cable GenSPEE 10 MTP or equivalent). • All cabling shall terminate to County IT approved modular jacks (Panduit Mini-Com UTP RJ45 Cat 6A TG or equivalent). Jack color shall match wall plates. Wired to TIA/EIA 568B scheme. • Ensure all Low Voltage Cabling is installed to the latest TIA/EIA 568 and TIA-569 standards using the latest BICSI-proposed installation procedures. • Ensure all work and materials are in accordance with the latest NEC, Federal, State and Local codes. • All Cabling shall be combed and bundled. • All terminated cables shall be individually labeled at each wall plate and patch panel, following the County approved naming convention. Labels shall be of a thermally printed type or other County approved method. • All Patch Panels shall be labeled following County IT provided naming convention. Labels shall be of a thermally printed type or other County approved method. • All cabling shall be installed in accordance with the manufacturer’s guidelines for bend radius and support.