A. Installation Standard: ASTM C754, except comply with framing sizes and spacing indicated. B. Gypsum Board Systems: Comply with requirements in ASTM C840 applicable to framing installation. C. Sound Insulation: Install sound attenuation blankets before installing gypsum panels, unless blankets are readily installed after panels have been installed on one side. D. Gypsum Ceiling Panels: 1. Comply with ASTM C840. Examine panels before installation. Reject panels that are wet, moisture damaged, and mold damaged: a. Install ceiling panels across framing to minimize the number of abutting end joints and to avoid abutting end joints in central area of each ceiling. Stagger abutting end joints of adjacent panels not less than one framing member. b. Install panels with face side out. Butt panels together for a light contact at edges and ends with not more than 1/16 inch (1.5 mm) of open space between panels. Do not force into place. c. Locate edge and end joints over supports, except in ceiling applications where intermediate supports or gypsum board back blocking is provided behind end joints. Do not place tapered edges against cut edges or ends. Stagger vertical joints on opposite sides of partitions. Do not make joints other than control joints at corners of framed openings. d. Form control and expansion joints with space between edges of adjoining gypsum panels. e. Cover both faces of support framing with gypsum panels in concealed spaces, except in chases braced internally: 1) Unless concealed application is indicated or required for sound, fire, air, or smoke ratings, coverage may be accomplished with scraps of not less than 8 sq. ft. (0.7 sq. m) in area. 2) Fit gypsum panels around ducts, pipes, and conduits. 3) Where partitions intersect structural members projecting below underside of floor/roof slabs and decks, cut gypsum panels to fit profile formed by structural members; allow 1/4-inch to 3/8-inch (6.4 mm to 9.5 mm) wide joints to install sealant. f. Isolate perimeter of gypsum board applied to nonload bearing partitions at structural abutments, except floors. Provide 1/4-inch to 1/2-inch (6.4mm to 12.7mm) wide spaces at these locations, and trim edges with edge trim where edges of panels are exposed. Seal joints between edges and abutting structural surfaces with acoustical sealant. g. Attachment to Framing: Attach panels so leading edge or end of each panel is attached to open (unsupported) edges of stud flanges first.