A. ROUTINE/WEEKLY SERVICES: The Contractor shall perform routine / weekly services within (1) one week of receiving notification from the Contract Manager once the contract is executed. B. WEEKLY INSPECTION SERVICES DESCRIPTION NFPA 25 CA Reference Pump house heating and ventilating louvers 8.2.2 (1) (a) - 8.2.2 (1) (b) Control Valves - Identification sign 13.3.1 Control Valves - Inspection 13.3.2 Pump suction, discharge & Bypass Valves open 8.2.2 (2) (a) Normally closed valves are closed (Test header/venturi meter) 8.2.2 (2) (g), 13.3.2.2 Valve Supervisory Devices 5.2.5 Piping is free of any leaks 8.2.2 (2) (b) Suction reservoir is full 8.2.2 (2) (e) Suction line pressure gauge reading within acceptable range 8.2.2 (2) (c) Suction pressure reading 8.2.2 (2) (c) System line pressure gauge reading within range 8.2.2 (2) (d) System pressure reading 8.2.2 (2) (d) Wet pit suction screens unobstructed and in place 8.2.2 (2) (f) Verify pump packing glands for slight discharge (Pump not running) 8.2.2 (2) (h) Suction pressure gauge reading (Pump running) 8.3.2.8 (1) (a) Adjust gland nuts if necessary 8.3.2.8 (1) (c) Check for unusual noise or vibration 8.3.2.8 (1) (d) Check packing boxes, bearings or pump casing for overheating 8.3.2.8 (1) (e) Circulation relief valve operating properly (No Flow) 8.3.3.2 (1) (a) Pressure relief valve operating properly (No Flow) 8.3.3.2 (1) (b) Pressure relief valve operating properly (Flowing) 8.3.3.3.1, 8.3.3.3.2, 13.5.7.2