1. Fire Alarm System Inspections and Testing a. General Scope Description: Service Provider shall inspect and test all fire alarm system components within all buildings included on the Fire Alarm & Sprinkler System Inventory – the “work”. b. Testing & Inspection Frequency: Service Provider shall perform one test per year on each automatic initiating device (heat, smoke, duct smoke, manual pull stations and beam/optical smoke detectors & sensors, etc.,) and one functional test on each notification appliance (horn, strobe, etc.) excluding a decibel level test. Testing shall also include one test per year on each fire protection/sprinkler system initiating device connected to and supervised by the fire alarm system; such tests shall be conducted electrically. The Service Provider shall provide semiannual testing of all fire alarm panel and power supply batteries. Install an inspection sticker with date and type of inspection. All testing shall be completed in accordance with the most recent edition of NFPA 72 – National Fire Alarm Code. 2. Smoke Detector Cleaning 3. Fire Sprinkler System (Wet Type) Testing & Inspection