Specifications include, but are not limited to: 1 Tank Construction type with secondary Interstitial containment meeting all California State and Federal requirements and fire ratings, mounted on steel saddles and enqineered hurricane tie downs Tank shall be coated with 940 DTM Polyaspartic Urethane in Grey color. 2 Tank Finish Coating must be fully capable to resist harsh weather conditions of subzero temperatures, ice and snow. 3 UL Listed Tank shall be listed with the Underwriter Laboratories and labeled UL 2085 Tank shall have an 18" Manway for access to interior of tank, (2) 8" 80z Emergency Vent Male w/0-ring, (1) 2" Stack Vent (12' above grade) w/2" Mushroom Cap (1) 2" Overfill Valve w/3" Male Quick disconnect w/4" Threads$ 2" Diffuser 4 Tank Configurations (1) 2" 918 Clock Gauge w/Alarm & Standard Float for Accurate Fuel level Reading (1) 7.5 Gallon Overspill w/lockable cap EQ.#726 (1) Interstitial Leak Gauge (1) Monitoring Well w/2" Cap (1) Ladder w/Platform and Safety Shield System shall be compatible with Diesel #2 Fuel with Winterization additives, Total Control 682-15 Piston Meter with 10:1 Pulsar, UL Listed Dispensing Box Welded on Tank 3'6"x4'2"x6'6", Cross Broken for Easy Drainage, 2" 5 Fuel Dispensing System Vent, 2"Mushroom Cap, & %" Ball Valve. (1) FE Petro% HP Pump Assembly w/anti-syphon valve & ball valve. (1) Hannay Hose Reel with 25' Hose, Ball Stop, 1" Nozzle, 1" Breakaway and 1" Swivel. (1) Electric Package for Pumps and switches, and Spin-on Filter(s) (1) ROM Door Roll-Up for fuel equipment compartment 3'x6'