Specifications include, but are not limited to: T-TAP 3 POSITION 1. THE ENCLOSURE SHALL BE FABRICATED WITH A MINIMUM OF 12 GAUGE STEELWITH A MINIMUM 2" 10 GAUGE CHANNEL BASE. THE ENCLOSURE SHALL BE DESIGN AND BUILT IN ACCORDANCE WITH AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) STANDARD C57.12.28, LATEST REVISION. THE NOMINAL DIMENSIONS OF THE ENCLOSURE ARE 48 INCHES WIDE BY 22 INCHES DEEP BY 30 INCHES HIGH. THE FOOT PRINT AND MOUNTING HOLES SHALL ALIGN WITH THE "COVER FOR 3-WAY T-TAP" PER SMUD DRAWING UVC2.2, LATEST REVISION. 2. THE CABINET SHALL BE SAND BLASTED PRIOR TO PAINTING AND SHALL INCLUDE A MINIMUM 2MIL ZINC COATING PRIMER, AND 2 MIL MINIMUM POLYURETHANE FOREST GREEN FINISH COAT OR SMUD APPROVED EQUIVALENT. 3. THE ENCLOSURE SHALL BE REINFORCED TO PREVENT EXCESSIVE FLEXING WHILE OPERATING ELBOWS. 4. THE CABINET DOORS SHALL INCLUDE STANLESS STEEL HINGES AND A PENTA-BOLT LOCKING SYSTEM WHICH ALSO ACCOMMODATES A PADLOCK WITH A 5/16" DIAMETER SHACKLE WITH A LENGTH OF 1 1/4". 4. PRIMARY JUNCTION ENCLOSURE SHALL HAVE THREE THREE-POSITION LOADBREAK JUNCTION BARS. THE THREE POSITION LOADBREAK JUNCTION BARS SHALL BE ELASTIMOLD NO. 164J3-5 OR APPROVED EQUAL. JUNCTION BARS SHALL BE RATED 8.3/14.4KV, 95 KV BIL AND HAVE 200A LOADBREAK CAPABILITY. THE JUNCTION BARS SHALL BE MOUNTED AT 12-1/2 DEGREE ANGLE. 5. THE ENCLOSURE SHALL HAVE SIX STAND-OFF LOCATIONS. THE PARKING STANDS SHALL BE SINGLE PARKING STANDS OR DOUBLE PARKING STANDS WITH STIFFENERS ADDED TO PREVENT THE STANDS FROM DEFORMING. 6. THE ENCLOSURE SHALL HAVE GROUND PROVISIONS THAT CONSIST OF TWO STAINLESS STEEL PADS (GROUND PADS), EACH WITH A 1/2 INCH 13 UNC TAPPED HOLE, 7/16-INCH DEEP. THE GROUND PADS SHALL BE LOCATED ON THE BACK WALL OF THE ENCLOSURE. THE INSIDE OF THE GROUND PAD SHALL NOT BE PAINTED. 7. GROUND CONNECTORS SHALL BE INSTALLED IN EACH GROUND PAD. CONNECTORS SHALL BE PENN UNION CATALOG NO. LSN-050NEJAM, OR DISTRICT APPROVED EQUAL, TO TAKE A 1/0 AWG STRANDED COPPER GROUND BUS. THE CONNECTORS SHALL BE INSTALLED TO SUPPORT THE BUS AT A DISTANCE OF THREE INCHES FROM THE FACE OF THE ENCLOSURE. THE WIRE GROUND BUS WILL BE PROVIDED AND INSTALLED BY THE DISTRICT. 8. BOTH GROUND PADS SHALL BE AT THE SAME HEIGHT ON THE ENCLOSURE AND THEY SHALL HAVE A MINIMUM HORIZONTAL SEPARATION OF 24 INCHES. 9. THE GROUND PADS SHALL BE AT SUFFICIENT HEIGHT SO THAT OPERATING PERSONNEL CAN ATTACH PERSONAL GROUND CLAMPS TO THE BUS, USING AN EIGHT-FOOT HOT STICK HELD AT WASTE LEVEL WITHOUT INTERFERENCE. PADS SHALL BE NO CLOSER THAN FOUR INCHES FROM THE SIDE-WALLS OR ANY COMPARTMENT BARRIERS. 10. THE ENCLOCURE SHALL HAVE LOUVERS TO ALLOW AIR FLOW INTO THE UNIT. LOUVERS SHALL PREVENT ANIMALS AND INSECTS FROM ENTERING THE ENCLOSURE. ONLY MANUFACTURES LISTED ARE APPROVED SCOTT ENGINEERING DRAWING 130803-1 (15KV) OR SMUD APPROVED EQUAL.