Specifications include, but are not limited to: Circuit breaker, 230-kV nominal, 3,000-ampere, 63-kA interrupting capability, 1.0 per unit continuous, nominal overvoltage capability, 250-VDC control voltage and 240- VAC auxiliary power, furnished with positive pressure of sulfurhexafluoride gas* (SF6) for shipment, dead-tank with silicone-rubber-housed bushings and four bushing-mounted W/X/Y/Z 3000:5 ratio current transformers (3 relay, 1 metering) ,gas density interlock switches and alarms, two separate trip coils, freestanding control cabinet, with support frame including forklift tubes, for a price per each of: *The LADWP will self-provide SF6 gas for the breakers when installed. "Siemens Energy" SPS2S-245-63-1.001