Specifications include, but are not limited to: Removal and disposal of (1) existing Rite Boiler model WG-600, 6,000,000 BTU Input. Include all rigging/hauling fees. 2. Delivery, Offloading, Rigging, and Placement of (1) Parker Boiler model #T5700 Industrial Packaged Hot Water Boiler, Direct Fired, with the following features and trim items: a. 5,700,000 BTU min Input requirement b. Natural Gas Fired, 14” W.C Max inlet pressure to gas train c. CSD-1 trim and Controls d. ASME “H” Stamp, with ASME safety relief valve. e. Barometric Damper, with gas spillage switch f. Indicator Lights g. Dry contact terminals for remote enable/disable h. Electric Modulation, fully modulating firing rate control i. Second Cabinet Door for service and access.