Specifications include, but are not limited to: Contractor will provide a Kohler 125 kilowatt diesel powered standby/ backup generator 208D/120 volt 3 phase, external 1,500 gallon diesel fuel stand-alone tank, 400- 430 amp automatic transfer switch, and cabling/wiring connecting the generator set to the main distribution panel according to the Unified Facilities Criteria (UFC). Installation will include moving an existing hazardous materials locker approximately 60 feet east on the existing asphalt and concrete apron freeing space for the new gen-set and tank. Genset will include internal radiator mounted 50% load bank, extra weather hood, heated enclosed with electrically and mechanically controlled louvers, and an extra circuit breaker specifically for the load bank. Refer to the detailed Scope of Work attached elsewhere in the bid documente for the generator, the enclose, the fuel tank, trenching, the automatic transfer switch and moving the haz-mat locker