Specifications include, but are not limited to:Furnish water treatment, chemicals (including Declarer required to remove silica and other materials from condenser ref. tubes), and required equipment and consulting service for operation of the boilers, water cooling towers (to include cooling tower sanitation for Legionella Disease testing quarterly), condensers and associated circulation systems for the heating and cooling equipment. 6.0 TOWER WATER TREATMENT: 6.1 Inhibitor (Low MOLYBDENUM/PHOSPHONATE based, e.g. 2-4 PPM as Phosphonate). All phosphate programs are not acceptable. 6.1.1 Provide treatment levels, recommended feed points, container size, material and type. 6.2 Dispersant – Liquid. 6.2.1 (You may propose a one drum treatment approach). 6.3 Biocide 1 (Stabilized Bromine or dual product equivalent) Apply at least twice per week at sufficient quantity to achieve a 3 ppm free residual, however you are required to feed sufficient material to meet biological goals. Due to the fact the pH of the tower water will be greater than 8.3 at full cycles; Sodium Hypochlorite feed without Sodium Bromide is not acceptable. If you plan to feed an alternate solid material, you must provide brominators for all towers. These can remain your property at the end of the contract. State terms for buyout if contract is ended. If dual feed is proposed, you must include the 1 additional pump for the sodium bromide. Again, these can remain yours, so state terms for buyout if contract is ended. 6.3.1 Provide Min/Max. level in PPM, active ingredients, container size, material & type, and recommend dosage schedule in days (i.e. Mon & Thurs. adds). 6.4 Biocide 2 (Glutaraldehyde) Use 45% fed at 120 PPM once per week. 6.4.1 Provide Min. /Max. levels in PPM, active ingredients, container size, material & type, and dosage schedule.