Offeror to supply, install and test a full operating Air-Cooled (HVAC) system. Quantity (2) Liebert PDX Air-Cooled System or approved equivalent. Electrical Requirements: 36.9 FLA, 43.7 WSA, 50 Amp OPD. • Configuration Number: PX029UA1A8H22801PLBSP09W3 • Model Number: PX029UA1A809W3 • Nominal 101 kBtuh (29.6 kW) at approximately 75°F, 45% RH • 460 Voltage, 3 Phase, 60 Hz System Details: • Upflow with Front Air Return • Liebert iCOM Control with High Definition Display • iCOM based communication o BACnet IP (Ethernet Port) o BACnet MSTP (RS-485 Port) o SNMP (Ethernet Port) o IP Protocols over one network • Variable speed EC plug fans • Digital scroll, variable capacity compressor utilizing R-410A • Crankcase Heater • Thermal Expansion Valve • Compressor Sound Jacket