Kohler Preventive Maintenance Minor Visit to include Inspection of all components Drain fuel/water separator Check & Record water level in main tank check operation of day tank Check fuel pressure check breather tube check air system piping check condition of dry type cleaner check engine oil level check for oil leaks clean batteries & cables check specific gravity add distilled water check operation of float charger check & record battery voltage under load visually inspect system check coolant level check for coolant leaks check radiator cap check circuit breaker operation check condition of exhaust system check condition of turbocharger check for exhaust leaks check exhaust rain shield check for wet stacking visual inspection of condition perform transfer test check all alarm lights perform non-contact temperature measurements vacuum debris check gauges & meters operation clean control cabinet check controls operation check shutdown systems check indicator & panel lights check/record frequency & voltage Kolher Generator350ROzd, 350KW3 Minor Visits From October 2025- September 2026; Kohler Preventive Maintenance Change fuel filter elements check for water in day tank check breather tube drain air box reservoir check air system piping service oil bath air cleaner change filter element change engine oil & filter check engine oil pressure oil laboratory analysis Change rotor & cap change spark plugs points & condenser check specific gravity of cells add distilled water check operation of float charger check & record battery voltage under load change coolant filter test antifreeze coolant testing samples vacuum debris check condition of bearing check condition of AC/DC brushes measure non contact temperature Kolher Generator350ROzd, 350KW1 major Visit From October 2025- September 2026; Kohler PM Fuel Sample Kohler PM Fuel Sample DFP11 Kolher Generator350ROzd, 350KWFuel Sample DFP11From October 2025- September 2026; Kohler PM Coolant Analysis Coolant Analysis Kolher Generator350ROzd, 350KWFuel Sample DFP11From October 2025- September 2026; Cat Generator PM Minor Visit to include Inspection of all components Drain fuel/water separator Check & Record water level in main tank check operation of day tank Check fuel pressure check breather tube check air system piping check condition of dry type cleaner check engine oil level check for oil leaks clean batteries & cables check specific gravity add distilled water check operation of float charger check & record battery voltage under load visually inspect system check coolant level check for coolant leaks check radiator cap check circuit breaker operation check condition of exhaust system check condition of turbocharger check for exhaust leaks check exhaust rain shield check for wet stacking visual inspection of condition perform transfer test check all alarm lights perform non-contact temperature measurements vacuum debris check gauges & meters operation clean control cabinet check controls operation check shutdown systems check indicator & panel lights check/record frequency & voltage Gen 2 CAT Generator 3412 380KW Serial Number 81Z210084 63 Minor Preventive Maintenace visits From October 2025- September 2026