Specifications include, but are not limited to: 2. Walls and Partitions 2.1 All 1-hour fire rated corridors shall meet County inspector’s requirements including but not limited to fire rating of matelines. 2.2 Wall mounted recessed fire extinguisher boxes as required by Code. 2.3 Classrooms will be minimum 650 square feet. 2.4 Ceiling height shall be 8’-0” minimum. 2.5 Floor to underside of beam shall be 8’-0” minimum. 2.6 New wall and ceiling paint. 2.7 Fiberglass reinforced plastic (FRP) in wet areas throughout. 2.8 One file storage room at entry office area for each school (approximately 4’ x 8’) must be two-hour fire rated. 2.9 Sound attenuation panels in a material approved by the Fire Marshall for flame spread in the corridors and multi-purpose spaces. 2.10 Contractor to submit with bid architectural floor plan layouts for each modular building (with dimensions shown). 3. Interior Doors 3.1 36” x 80” 20 minute with self-closing hinge. 3.2 Lever Hardware – 7 pin keyway cores. 3.3 Door hardware to accept owner’s Best cores. 4. Exterior Doors 4.1 72” x 80” steel/steel exterior doors with 4” x 24” view block with continuous hinge (piano style) and removable center post and closures. 4.2 Panic device – Von Duprin or approved equal. 4.3 Double doors on exterior shall not have hardware that can be chained together. 4.4 Levers with 7-pin keyway cores. 5. Flooring 5.1 Flooring shall be like new VCT flooring or approved equal and like new vinyl base. Carpet is not permitted, other than in the library and enclosed offices where it is preferred. Carpet shall be commercial grade.