Specifications include, but are not limited to: closure of existing 1,000 gallon UST and furnish and installation of (1) new 3,000 gallon AST. furnish and install one (1) new 3,000 gallon double-walled steel Above ground Storage Tank and closure of currently used 1,000 gallon UST. All equipment, materials and installation work shall comply with this specification, the Virginia OSHA Standards, DEQ requirements and the Virginia Uniform Statewide Building Codes.” Reuse existing suction dispenser, card reader and tank monitor. Reuse existing conduit and wiring at suction pump. Add new data cable for sensors and probe with upgrade module in existing tank monitor. Install 4000 psi concrete pad 26’x14’x8” with # 4 rebar 12”oc. Install 6”x7’ with 4’ revealed pipe bollards 4’ on center 3’ off tank. Install 3,000 gallon double wall tank with steps and platform with decal package. Install spill containment with overfill drop tube, emergency vents, tank probe, interstitial sensor, vent, manual tank gauging port and clock gauge with audible alarm. Install 1-4’Wx5’Lx9”H carbon steel island. Install dispenser sump with sump sensor, 1½” double wall pipe and access pipe, one (1½”) anti-siphon valve and emergency valve. Equipment reset, programmed and started up.