Specifications include, but are not limited to: Four (4) reels of 750MCM 15KV EPR Power Cable, with 1/3 Neutral Construction. a. Basic Construction: 15kV, 1/3 neutral, 750 MCM power cable. b. Conductor: 750 kcmil, stranded aluminum conductor conforming to ASTM B231 for Class B stranding. Conductor shall be filled with a semi-conducting compound. c. Conductor Shield: Shall consist of an extruded layer of semi-conducting thermosetting compound with a minimum average thickness of 40 mils. d. Insulation: Insulation shall consist of 220 mils of EPR. e. Neutral: The neutral shall consist of a balanced, helical wrap of un-coated copper wires with conductance equal to 1/3 that of the main conductor. f. Jacket: A polyethylene jacket shall encapsulate the neutral wires with a minimum thickness of 70 mils. g. Sequence printed with footage. h. Supply cable construction diagram and the over insulation diameter dimensions. i. Three conductors to be paralleled on wooden reels, per required circuit foot lengths as listed below. Length tolerance shall be +2 ½% -0. Include reel cut charges that may apply as a separate charge. One reel shall be paralleled on a steel reel. i. One (1) Reel 730’ ii. One (1) Reel 800’ iii. One (1) Reel 340’ iv. One (1) Reel 530’