Specifications include, but are not limited to: 1. Pole Building type construction. 2. Painted galvanized 29 gauge steel walls and roof. Minimum radiant barrier insulation of walls and roof. 3. Minimum 2x6 purlins and girts; purlins minimum 24” on center; girts minimum 24” on center 4. Square feet: Minimum 1500 (e.g., 30 x 50) 5. Ceiling Height: 12 foot eave height, minimum 11 foot ceiling clearance. 6. Site Prep: Includes removing existing sod and topsoil, replacing with appropriate subgrade and subbase gravel for concrete slab with top of slab at least 6 inches above surrounding grade at its highest point. 7. 4 inch minimum concrete slab to accommodate building plus an additional 12’ on the north side of the building (drains away from the building 0.5%) approximately 240 square feet. 8. Rodent exclusion design (Describe solutions and plans for how holes, cracks, etc. through which rodents can infiltrate will be eliminated) 9. Two regular doors 42” wide x 7’ high. One each on northwest and southwest gable sides. 10. Two overhead garage doors 12’ X 10’. Both on south side gable. 11. Two to four translucent roof panels for natural light in the space. 12. Option #1: Extend regular roof to cover the 12 foot extension, or add lean-to covering that is at least 8 feet high at low side.