Specifications include, but are not limited to: • Spec for installation of a complete Wet Type NFPA 13 Fire Suppression System for above ground structure. • Contract to start at 6” flange located in mechanical room, above finished floor and out to Wet System. • Fire Riser complete to include state improved double check backflow assembly w/tamper switches on control valves, flexible couplings at base and top of riser assembly, flow switch, fire dept. connection “FDC” piped to exterior in an acceptable location AHJ, main drain piped to exterior and exterior electrical weather proof horn strobe outside riser room at required height and location. • Design complete system including shop drawings (with a min. 1/8” = 1’), hydraulic calculations with min. 10% safety factor, hydrant flow test per NFPA 291, designed for Ordinary Hazard Grp. II (building not to be used for storage, but fir archery with minimal combustibles). Design to follow the requirements of NFPA 13, 2013 edition. Shop drawings and calc’s to be approved by owner and AHJ prior to ant fabrication or installation and approved plans to be onsite at all times.