Specifications include, but are not limited to: 1. Safe removal and disposal of the existing Computer Room Air Conditioning Unit (CRAC) 2. Install the new Computer Room Air Conditioning Unit (CRAC) unit and make all necessary connections including electrical, air ducts, and control system. ; 1. Liebert Model #FH125A-AS00 complete with Blower intake, Grille plenum cooling coils, semi-hermetic compressor, Insulated cabinet, V-belt drives, high efficiency motors, Unit controls, Filter racks with filters. ii. Cooling 1. 10 nominal tons total cooling capacity at 60 degrees EWB, 72 degrees EDB, 5650 CFM at 29.7 GPM 45 degree EWB, 10 degree rise 4 row, 11.7 sq. ft. cooling coil, 431 ppm(face vel) (std rating conditions) 1-1/4”cu water connections. iii. Supply Blower 1. 6050 CFM s.a. at 3 in. wg. External (std air) external variable pitch, 2 belt drive, adjustable RPM (std air) 3 hp, 480v 3 phase single speed motor.