Specifications include, but are not limited to: Design: Provide cable designated as THHN/THWN-2 single conductor type and UL 83 and UL 1063 listed, rated 600 volts and certified for continuous operation at a maximum conductor temperature of 90 degrees C in dry locations and 95 degrees C in wet locations while installed in underground duct, in above ground conduit, or in control panels (MTW) in accordance with NEC Articles 210 and 310. The conductor shall be rated for use in 75 degree C oil or coolant applications. Conductors. Provide conductors, which are Class B, concentric, stranded (solid conductor will not be acceptable), soft-drawn annealed, un-coated, copper 98 percent conductivity with physical and electrical properties complying with ASTM B3 and B8 and Part 2 of ICEA S-61-402. Each wire shall be continuous without a weld, splice and or joint throughout the length and it shall be uniform in cross section, new unused and free from flaws, scales and other imperfections. All wiring shall comply with UL standards and shall bear its stamp of approval, size, type and voltage rating. Insulation. Each conductor shall be PVC insulated and nylon jacketed to meet the requirements of Part 3 of ICEA S-61-402. The insulation thickness shall match the dimensions listed in Table 310-15 of NEC 2014 for type THHN and THWN-2 wire. Metal Clad (MC) and Armored Cables (AC) shall be furnished and installed with 600 volt, THHN/THWN-2, copper, stranded conductors. A green ground stranded, copper conductor shall be furnished and installed with phase and neutral wires.