Specifications include, but are not limited to:The Work consists of providing a 3,000 ton modular chilled water plant and cooling towers located at the Austin Convention Center on the lower roof adjacent to the loading areas on the east side of the facility. The plant shall be connected to the existing chilled water distribution system located under Red River Street by April 2019. The plant shall be built in a factory environment and consist of a modular building capable of housing the two chillers, three condenser pumps, three variable primary pumps, chilled water side stream filter/pump, piping, controls, and electrical switchboard and distribution. The plant shall have also be provided with stub outs for connection to the existing chilled water distribution system located under Red River Street, cooling towers, makeup water and electrical. Three cooling towers located adjacent to the modular building shall be provided. Each cooling tower shall be provided with a basin sweeper system with pump. See Section 01010, Summary of Work for a detailed description of the Work.