Specifications include, but are not limited to: 1.Inlet MAOP:500 PSI2.Outlet MAOP:125 PSI3.Fisher ANSI 300 EZR Regulators (Worker and Monitor Run)4.Fisher ANSI 300 EZR Regulator – Regulated Bypass Run5.Fisher ANSI 150 Relief Regulator6.Full Port, Weld x Weld Ball Valves7.Station shall be tested at a minimum of 750 psig.8.Station shall be painted with TNEMEC primer and paint. Primer shall beSeries 161, and top coat shall be Series 740 UVX – gray.9.Shall include thread-o-lets for inlet pressure, outlet pressure, temperature,and an extra port on the inlet and outlet side of the station.10.Shall include a rain cap w/ indicator.