1. DEMO EXISTING ELECTRICAL WORK AS NEEDED TO ACCOMMODATE NEW CONSTRUCTION. 2. ALL POWER & LIGHTING CIRCUITS ARE #12 CONDUCTORS IN 1/2" CONDUIT OR MC CABLE, UNLESS OTHERWISE NOTED. WIRING SHALL BE CONCEALED IN FINISHED AREAS. INSTALL A GREEN GROUNDING CONDUCTOR IN EACH CONDUIT. 3. MAINTAIN MINIMUM 3'-0" CLEARANCE IN FRONT OF PANELS FROM FLOOR TO CEILING. PIPING, DUCTWORK, ETC. IS PROHIBITED IN THIS AREA. 4. ALL SERVICE ENTRANCE AND FEEDER CONDUCTORS GREATER THAN 100A MAY BE SUBSTITUTED WITH PROPERLY SIZED ALUMINUM CONDUCTORS. 5. ALL MECHANICAL EQUIPMENT MUST BE CAPABLE OF BEING DISCONNECTED FROM ITS POWER SOURCE. 6. COORDINATE ELECTRICAL WORK IN MECHANICAL ROOMS WITH MECHANICAL CONTRACTOR. 7. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ONLY INDICATE A GENERAL ARRANGEMENT OF THE EQUIPMENT AND WIRING. DO NOT SCALE FROM THE DRAWINGS. IT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO PROPERLY FIELD LOCATE ALL COMPONENTS OF THE ELECTRICAL WORK BASED ON CODE REQUIREMENTS, MANUFACTURERS INSTALLATION INSTRUCTIONS, AND COORDINATION WITH SITE CONDITIONS AND OTHER TRADES. 8. THIS PROJECT CONSISTS OF EXTENSIVE RENOVATION WORK. THE NEW WORK SHOWN IS DIAGRAMMATIC ONLY, AND MUST BE COORDINATED WITH EXISTING FIELD CONDITIONS. EXISTING WORK IS SHOWN FOR REFERENCE ONLY AND HAS NOT BEEN VERIFIED. THE CONTRACTOR SHALL VISIT THE JOBSITE AND COMPLETELY FAMILIARIZE HIMSELF WITH THE COMPLETE SCOPE-OF-WORK, BOTH NEW AND EXISTING BEFORE SUBMITTING BID