Specifications include, but are not limited to: Installation of a new Fire Sprinkler System throughout the existing building. Small and Minority Business participation is highly encouraged. A. This section of these specifications is intended to describe for furnishing labor, material, and equipment for the installation of a wet pipe automatic sprinkler system and a dry pipe automatic sprinkler system. B. In all areas, piping shall be located high in the space to minimize the future impact of the air conditioning, heating, ventilating and electrical systems that must occupy the same general areas. C. Contractor shall design an automatic sprinkler system for the entire building as indicated on the plans. All piping shall be sized based on hydraulic calculations using 80 PSIG static and 42 PSIG residual at 1040 GPM. These pressures and flow are theoretical as the owner is currently installing a new water service to join to city mains. New water line drawings may be obtained from the owner for use in the hydraulic calculations.