2.1 UPS System Specifications Specifications include, but are not limited to: .1 Input Voltage: 480V, 60Hz, 3-phase, 3-wire plus ground .2 Output Voltage: 208/120V, 3-phase, 4-wire plus ground .3 Capacity: Fixed capacity 40kVA UPS system .4 Architecture: Transformer-free, efficiency up to 95% in double conversion mode .5 Output Power Factor: Unity rating; supports loads from 0.5 lagging to unity without derating .6 Native Output Voltage: 208V .7 Bypass Switch: Continuous duty static bypass .8 Controls: DSP-based digital control of power conversion and operation .9 Display: Backlit LCD with monitoring and logging of power, operation, and utility conditions .10 Access: Top-and-bottom-entry cable access; front-only service access .11 Safety Features: Local Emergency Power Off (EPO); IP20 enclosure .12 Certifications: UL and cUL listed, UL Standard 1778 5th Edition