Specifications include, but are not limited to: POTABLE WATER TREATMENT: Fixed fee Chemical Treatment Equipment & Service Agreement Including • Potable Corrosion Inhibitor – Drum Delivery (5-6) 55 Gal. Drums, 625 lb’s. each • Laboratory Supplies & Test Reagents • Monthly Service Visits Boiler Systems Operating Information: Boiler House (3 – Water Tube Keeler Boilers) - 2 – 300 HP - 1 – 350 HP - One Lead/One Lag - Annual Operation – 210 Days/Year - Average Total Daily Steam Production – 650,000 lbs./day - Average Operating Cycles of Concentration – 15 Cycles - Condensate Return – 65% - 75% - Feedwater hardness - <0.1ppm - Make – Up Water Hardness - <1.0ppm - Operating Boiler Pressure – 80 – 100psi - Deaerated Feedwater Dissolved Oxygen – <10ppb Laboratory Reagents and Hardware All laboratory reagents, Pacesetter maintenance and test hardware required to perform daily testing will be provided to Mansfield University by vendor and included in the annual fixed price agreement.