Specifications include, but are not limited to: 1. Store materials not in actual use in an appropriately secured manner. 2. All material stored on site will be protected from weather elements. 3. Take precautions to ensure that workmen and work areas are adequately protected from fire hazards and health hazards resulting from handling, mixing and application of any roofing material. 4. All flammable materials shall be stored in approved containers. 1. Pole Building size shall be 40’ W x 80’ L x 16’5” H 2. Total Square feet under roof to be 3,200 square feet 3. Roof pitch to be 4/12, standard trusses 1. All structural members, such as but not limited to headers, supports and rafters to be #1 southern yellow pine or better. 2. All non-bearing members, such as but not limited to girts, purlins and door soffits to be #2 SPF 3. All dimensional lumber is to be CA treated material and attached with 20d galvanized ring shank nails. 4. One 2” x 10” pressure treated splash board attached to foundation column around entire perimeter at grade. 5. Required Uniform Construction Code compliant fasteners used at all connections