Specifications include, but are not limited to: Slippery Rock University of Pennsylvania is seeking bids for a NKT STADIUM ELECTRICAL GEAR REPLACEMENT MAIN SWITCHBOARD SPECS BELOW AND THREE (3) ATTACHED DOCUMENTS. Provide pricing for a two (2) section, 1200 amp, 480/277 VAC, 60 Hz, 3-phase, 4-wire indoor switchboard, fully-rated for a short-circuit of 25 kA. The switchboard shall include customer metering, one (1) 1200 amp 3-pole molded case main circuit breaker with LSIG electronic trip unit and arc flash reduction, one (1) UL 1449 Type 2 surge protection device, and the following thermal-magnetic molded case, 3-pole branch circuit breakers; one (1) 400 amp, one (1) 350 amp, two (2) 250 amp, one (1) 200 amp, and one (1) 100 amp.