Specifications include, but are not limited to: All meter brass fittings shall be full port and of the same design as the corresponding fittings indicated. If make and model other than those requested are offered, the make and model are to be shown and the specification literature supplied for the fitting (s) offered. Exceptions must be equal to and interchangeable with the fittings requested. All brass fittings shall be manufactured “Low Lead Brass”. Disclaimer: All products received must meet Federal guidelines even if not stated in specifications. Split case iron tapping sleeves shall be 150 psi working pressure with a cast iron body conforming to ANSI/AWWA C110. Sleeve must have mechanical joints conforming to ANSI/AWWA C111 on the run and a flange branch conforming to ANSI B16.1, Class 125. Ends gaskets shall be natural rubber or neoprene material conforming to ANSI/AWWA C111. Tapping saddles for ductile pipe must be Mueller, Clow, American, Tyler, Powerseal, Smith-Blair or approved equal. Flexible stainless steel tapping sleeves shall be rated at 150 psi pressure, with flanges meeting AWWA 207. Assembly shall be NSF or UL rated. Bolts, nuts, and washers shall be stainless steel. Gaskets shall conform to ANSI/AWWA C111. Blind flanges must be fabricated from material as specified under ANSI/AWWA C200. Joint restrainers must be a wedge action type restrained joint assembly equal to the Megalug Series 1100 or the Ford Meter Box Uni-Flange Series 1400. Restrainers must have twist-off-nuts that break at a specific torque. Screw type retainer glands will not be accepted. Only American Flex Ring, EBAA Megalug, Ford Meter Box Uni-Flange, or Star StarGrip restrainers will be accepted. Tapped Full circle repair clamp double band couplings must be furnished with stainless steel nuts and bolts coated to prevent galling. Only Ford Meter Box, Rockwell, Powerseal, Smith Blair, Mueller, or JCM Ind. full circle clamp couplings will be accepted. Flange coupling adapters must be Smith-Blair or Powerseal. Other brands will not be accepted. Bell joint clamps must be Smith-Blair or Dresser. Other brands will not be accepted. Multi-couplings must be Powerseal or Romac. Other brands will not be accepted.