Specifications include, but are not limited to: COMMSCOPE Uniprise or comparable quality CAT6 Plenum Cable. Colors will be Blue for Data, Yellow for WiFi, and Green for cameras. Provide and install J hooks for access control cable where needed. Provide Patch Panels need to be labeled and color coded with corresponding cable. Will provide and install 48U two post rack mounted in IT Room 127 with location determined by customer. Wire ladders to support all cable in IT Room from wall to rack. Cable baskets to support cable in Mechanical Room 215. Rack, ladders, and wire baskets must be grounded to building ground. Provide planning assistance to the Town and site Construction Manager at Risk Contractor for the structure cable installation. Provide faceplates at cable destinations. All faceplates and patch panels must be labeled and tested. Cable terminations at device end to be determined by Owner. Provide proof of testing all network drops. Provide a As-Built for network drops at completion of job.