Specifications include, but are not limited to: Shall be minimum 12-1/2% trade solution complying with AWWA specification B300 (most recent edition) and certified to NSF/ANSI Standard 60 by an ANSIAccredited third party certifier. The hypochlorite shall contain no less than 1.00% or more than 1.05% of excess caustic soda by weight upon delivery. The seller agrees to furnish Manchester Water Works a copy of certified titration tests of each individual shipment. Said test must indicate the specific gravity and pH of the finished hypochlorite, the percent available chlorine, and the percent excess caustic soda, both by weight. Upon delivery, samples will be titrated to assure %-concentration of available chlorine. Additionally, the solution temperature will be measured upon delivery and is not to exceed 46.1oC (115oF) and shall be returned at the supplier’s expense or off loaded when the temperature reaches acceptable levels.