Specifications include, but are not limited to: The Contractor will be provided a PDF of drawings to bid from. The awarded bidder will be given a stamped and sealed plan set to mark up for as-build reference. The Contractor shall provide and install 400-amp 2 pole service entrance rated main lug panel board with copper buss bar. A 4” conduit is currently in place at grade on the West side of the shed, 20 feet from the North side of the building, and is fed from panel MDP next to the site transformer. The current contractor working in the park, Meyer Electric, shall pull (3)- 600KCMIL and (1) #4G conductors in conduit. Terminations of these conductors at panel MDP shall be done by Meyer Electric. Conduit runs and wire terminations in maintenance shed service entrance panel shall be done by bidding contractor. Meyer Electric shall provide a 400-amp breaker in panel MDP and will terminate wire in panel MDP once inspected by a County inspector. Wire pull to be coordinated with Meyer Electric site foreman. The Contractor is to provide and install (1) 400amp 2-pole main lug service entrance rated 42 space panel, one (1) 200amp 2-pole breaker for sub panel, one (1) 200amp 2- pole main lug 42 space panel. Contractor shall also provide and install necessary conduit from 4” stub outside building to panel. Spare breakers shall be provided in each panel and shall be single pole 20-amp breakers for future circuit additions. Ten (10) 20-amp breakers shall be installed MP panel for future use. Five (5) 20-amp breakers shall be installed in panel SP for future use.