Specifications include, but are not limited to: Item 1 (CU 130080) 10 KVA CONVENTIONAL POLE MOUNTED DISTRIBUTION TRANSFORMER. 1. PRIMARY VOLTAGE: 7620V/13,200 GROUND Y (95 KV BIL), TWO 2-1/2% TAPS ABOVE AND BELOW PRIMARY VOLTAGE. 2. SECONDARY VOLTAGE: 120/240V (30 KV BIL). 3. LOAD RATING AT 65 DEGREE C RISE, SINGLE PHASE. 4. 60 HERTZ OPERATION. 5. ONE SET OF MOUNTING LUGS. 6. TWO COVER MOUNTED BUSHINGS. 7. THREE STANDARD TANK MOUNTED SECONDARY BUSHINGS. 8. EACH DISTRIBUTION TRANSFORMER SHALL BE EQUIPPED WITH A NONRESETTABLE DEVICE; ITEM 2 (CU 130150) 25 KVA CONVENTIONAL POLE MOUNTED DISTRIBUTION TRANSFORMER. 1. PRIMARY VOLTAGE: 7620V/13200 GROUND Y (95 KV-BIL), TWO 2-1/2% TAPS ABOVE AND BELOW PRIMARY VOLTAGE. 2. SECONDARY VOLTAGE: 120V/240V (30 KV BIL) 3. LOAD RATING AT 65 DEGREE C RISE, SINGLE PHASE. 4. 60 HERTZ OPERATION. 5. ONE SET OF MOUNTING LUGS. 6. TWO COVER MOUNTED BUSHING. 7. THREE STANDARD TANK MOUNTED SECONDARY BUSHIN 8. EACH DISTRIBUTION TRANSFORMER SHALL BE EQUIPPED WITH A NONRESETTABLE DEVICE; ITEM 3 (CU 130220) 50 KVA CONVENTIONAL POLE MOUNTED DISTRIBUTION TRANSFORMER. 1. PRIMARY VOLTAGE: 7620/13,200 GROUND Y (95 KV BIL), TWO 2 1/2% TAPS ABOVE AND BELOW PRIMARY VOLTAGE. 2. SECONDARY VOLTAGE: 120/240V (30 KV BIL). 3. LOAD RATING AT 65 DEGREES "C" RISE, SINGLE PHASE. 4. 60 HERTZ OPERATION. 5. ONE SET OF MOUNTING LUGS. 6. TWO COVER MOUNTED BUSHINGS. 7. THREE STANDARD TANK MOUNTED SECONDARY BUSHINGS. 8. EACH DISTRIBUTION TRANSFORMER SHALL BE EQUIPPED WITH A NONRESETTABLE DEVICE