Specifications include, but are not limited to: Annual Generator Service, Inspection, and Analysis Performance Requirements: On an annual basis, the contractor shall perform generator service, inspections, and analysis to include but not be limited to the following. Fluids Analysis: Determine condition of engine fluids - fuel, oil, and coolant. Electrical Systems: Check battery electrolyte level and top off; Check and record battery voltage; Check and record battery charger amperage; Check battery connection terminals and clean as necessary; Clean battery post and terminals; Clean battery charger and adjust float rate if necessary; Clean and apply corrosion inhibitors to lead acid battery terminals; and Inspect and tighten starter motor(s) connections and wiring.