Specifications include, but are not limited to: a. Remove Bennett and Gasboy dispensers and associated equipment at SCFS and SLA respectively, remove Gorman Rupp motor, pump and associated equipment at CAF: Replace each with single product, single hose mechanical AvGas/100LL fuel pumps (Bennett 3000 Series Mechanical or approved equivalent) with Dispenser Pedestals (OPW Model No. PP-2136 or approved equivalent) at each location; i. Contractor shall provide verification from the manufacturer that pumps/dispensers are capable of dispensing AvGas; ii. New dispensers need only show fleet readings of gallons and tenths of gallons pumped, commercial dispensers with dollars and cents retail displays are not necessary; b. 50 feet of one and one-half (1 1/2) inch aviation grade fuel hose with swivels (Hewitt 4113 Aviation Fueling Hose or approved equivalent); c. Aviation grade non-automatic nozzles with strainer, dust cap and ground wire suitable for use with Avgas; d. Velcon Filter ACO-51201P, Velcon filter vessel VF61E (or approved equivalents) gaskets, piping and associated equipment as necessary; e. Static grounding reel w/50 feet of ground cable and clamp; f. Associated equipment as needed at each location; g. Veeder Root internal tank monitoring systems (TLS-4C or approved equivalent) at the CAF and SCFS tanks with installation and set up; h. CAF tank i. Remove existing Fuelmaster credit card terminal, replace with FuelMaster 2550 Plus, or approved equivalent, credit card fueling terminal; ii. New credit card terminal shall come with three (3) FuelMaster Prokees, or approved equivalent;