Specifications include, but are not limited to: Provide and install Flygt explosion proof submersible sewage pump with high chrome impeller and discharge ring. Pump shall be rated at 230 volt. Pump shall be equipped with seal fail and high temperature control with 50’ motor and sensor cables. Pumps shall be sized as follows: Location 684, 685, 686: 7.5 HP 3 phase pump, Flygt Model # 3127 6” discharge Location 692: 5 HP 3 phase pump, Flygt Model # 3102 6” discharge Location 691: 15 HP 3 phase pump, Flygt Model # 3153 8” discharge **NOTE: The Flygt pumps listed above are the ONLY specified manufacturer/model numbers acceptable for this bid Location 692 has an existing single phase electrical service. The control panel at that location shall include a Variable Frequency Drive (VFD) for phase conversion to accommodate a 3-phase motor. Provide and install 8” discharge elbow, 8” rubber flapper check valve and process piping from discharge elbow to check valve. Provide and install complete stainless steel guide rail system, stainless steel lift chain, stainless steel float rack, stainless steel quick link (based on 20’ wet well depth). Provide and install three normally open floats (On, Off, and High Water) with 50’ cable to the control cabinet.