Specifications include, but are not limited to: a. Direct Digital Control of Unit Ventilators • 62 classrooms • Install new Alerton VLC • Supply fan start/stop /status • Install new stainless steel space temperature sensor • Supply air temperature • Hot water valve control on existing valves • OA/RA damper control, reusing existing actuators • Install new communication line • Full commission report on all equipment • Deficiency list must be kept on all valves and actuators • Program and graphics will be customer preference b. Direct Digital Control for Gymnasium RTUs • 2 Trane Rooftops • Integration of the existing RTU BACnet controllers to transfer all available BACnet points from the Trane system to the Alerton system. All controls are existing. Integration of existing points only. • BAS contractor to work with TRANE representative for commissioning, testing, and operation of units. (Worcester Public Schools will provide Trane Technician.) • Deficiency list to be supplied to customer • Program and graphics will be customer preference