Specifications include, but are not limited to: 1. Lead and Copper Lead in Water Testing Services, in accordance with EPA guidance documents on "Lead in Drinking Water in Schools and NonResidential Buildings". Offeror shall demonstrate knowledge of relevant EPA guidance pertaining to Lead in Drinking Water in Schools. Protocol: Water samples collected by certified MDE water samplers; Water samples shall be collected in 1-liter containers that have been prepared by an accredited lab; Each water source (all water fountains throughout a school) must have a 1st and 2nd draw (flush) sample; and Allow the water to run at least 1 minute between first and second draws. 2. Other water tests will be requested as needed. 3. Consultant must develop a written water testing management plan containing the following minimum components: a. Critical milestones outlined with timelines. b. Sample schedule for the project. c. Root cause analysis protocol and communication for each outlet that is found not in compliance. d. Outlet shut-off confirmation status and tracking plan. e. Transport samples to the approved laboratory with chain of custody protocol. f. Communicate the results and generate and track action plans.