Specifications include, but are not limited to: Replace two (2) Uninterrupted Power Supply (UPS) units. he Department seeks to: Have the existing UPS unit at the primary 911 currently located in the telephone room relocated and installed in our radio room. Have the existing UPS unit at the backup 911 center disposed of. Have the vendor supply and install replacement UPS units which are compatible with our buildings’ electrical rating The two replacement UPS units will meet the following specifications: o 16 kVA rating Unit will not exceed average load rating of 30% o System input voltage 208/120V, Single Phase o System output voltage 208/120 V, Single Phase o Scalable battery system design o Run time for both units at least 40 minutes o The UPS units will include a power off switch to be utilized for emergency disconnect o One Maintenance Bypass with the following specifications: 150-175 Amp breaker trip rating Wall mounted to attach to module with factory supplied cables Front access service design Top and bottom entry cable access