Specifications include, but are not limited to: 1) Provide removal of (4) 2 pole 20 amp circuits from regular power panel controlling IDF room #005 in basement. 2) Provide removal of (3) 2 pole 70 amp circuits from regular power panel controlling IDF room# 059 on ground level. 3) Provide and install (1) 1.25" Flexible Metal Conduit w/ wire for (4) 2 pole 20 amp circuits for IDF room #005 in basement. 4) Provide and install (3) 1.25" Flexible Metal Conduit w/ wire for (3) 2 pole 70 amp circuits for IDF room #059 on ground floor. 5) Install the above mentioned circuits in the emergency generator panel in the electric room 026 on the ground floor. 6) Provide terminations of the line side and load side of the above mentioned circuits, 7) All wiring work to meet the requirements of the 2017 National Electric Code. 8) Test (2) Generator panel located in the room 026 ground floors for max load of existing circuits. Provide explanation of findings of the load test of each panel. This work should be performed prior to any of the above work performed to ensure the load capabilities of the existing emergency generator panel and associate circuits can hold the new loads to be installed.