Specifications include, but are not limited to: Perform a complete visual inspection of the equipment including internal sub-assemblies, wiring harnesses, contactors, cables, major components, and check for proper clearance around the unit. Perform an Infrared Scan (IR Scan) and verify all transformer, terminal block, and ground/neutral bus bar connections for tightness Perform an Infrared Scan (IR Scan) and verify all circuit breakers including the panelboard(s) branch circuits for tightness Perform an Infrared Scan (IR Scan) and verify high and low voltage junction box terminals for tightness (if applicable) Perform an Infrared Scan (IR Scan) and verify all option wiring for tightness. (Spike suppressor, ground fault, phase rotation/loss) Verify system control power fuses. (Equipment MUST be de-energized) Verify grounding electrode conductor and any isolated grounds. Verify EPO lamps are illuminated (if applicable).