Specifications include, but are not limited to: 1. Preliminary Design Report for a new Bidirectional 4160 Volt, 60 Hertz / 6600 Volt, 25 Hertz Voltage Pure Sinewave Static Frequency Converter in the power range of 20 to 25 Megawatts and all ancillary requirements, stamped by a Professional Engineer, to be turned over to SWBNO as property of SWBNO upon acceptance. 2. Selection and specification of a static frequency converter compatible with SWBNO’s existing electric motors. 3. Identify and determine the viability of a proposed location for the new equipment. All aspects location shall be studied from structural analysis to equipment clearances. 4. Design the switchgear additions and reconfigurations required for the integration of the new frequency converter into the existing system. 5. Design monitoring system for static frequency converter to integrate into existing SWBNO SCADA network. 6. Prepare design drawings and specifications for the purchase and installation of the equipment. 7. Plan for the integration of the new system functional design into the Board 60 hertz and 25 Hertz One-Line Diagram. 8. Design startup and phasing plan. 9. Furnish Contract Administration and Inspection Services during the construction phase.